Air Flow Switch This Control detects air flow or the absence of air flow in ducts, responding only to velocity of air movement. It has a One piece stainless steel paddle, which may be trimmed, if needed. Control supplied with mounting plate and gasket .
|
Max. Air Temp
|
180 F (82C)
|
|
Max. Air Velocity
|
2000 fpm (10 m/sec)
|
|
Dimensions
|
10 3/8" H (including paddle), 4" W, 2 3/4" D
|
Specifications
|
Paddle Width
|
Paddle Width
|
Minimum Air Velocity in FPM (m/sec) (required to Actuate Control)
|
|
Horizontal Flow
|
Vertical Flow (Upward)
|
|
50 inò (323 cmò ) or larger Duct Area
|
Less Than 50 inò (323 cmò ) Duct Area
|
50 inò (323 cmò ) or larger Duct Area
|
Less Than 50 inò (323 cmò ) Duct Area
|
|
2 1/8"
|
Increase (R to Y Closes)
|
635 (3.2)
|
575 (2.9)
|
950 (4.8)
|
750 (3.8)
|
|
Decrease (R to B Closes)
|
325 (1.7)
|
220 (1.1)
|
850 (4.3)
|
575 (2.9)
|
|
3 1/8"
|
Increase (R to Y Closes)
|
500 (2.5)
|
350 (1.8)
|
750 (3.8)
|
500 (2.5)
|
|
Decrease (R to B Closes)
|
250 (1.3)
|
100 (.5)
|
650 (3.3)
|
350 (1.8)
|
Electrical Ratings
|
Motor Rating in Amps.
|
120 V.
|
208 V
|
240 V
|
277 V
|
|
Nominal Horsepower
|
1.
|
1
|
1
|
--
|
|
A.C Full Load
|
16.0
|
8.8
|
8.0
|
--
|
|
A.C Locked Rotor
|
96.0
|
52.8
|
48.0
|
--
|
|
Non inductive or Resistance Load
|
22.0*
|
22.0*
|
22.0*
|
22.0*
|
|
Pilot Duty - 125 VA. 120/277 V.A.C.
|
|